Cause
EPLAN has determined a faulty bus port. Which PLC card is affected and which properties of the bus port may have to be corrected is specified in the placeholder "<x>" of the message.
Solution
- Locate bus port in the schematic using the Go to (graphic) functionality that is provided by the popup menu of the Message management dialog.
- Open the property dialog of the bus port.
- Bring the PLC connection point tab to the front.
- Check the value of the Plug designation property and correct it if necessary.
- Bring the Bus data tab to the front if errors in further properties apart from the plug designation are reported.
- Check the values of the properties specified in the message text and correct these (for example for the property Bus system or Bus interface: Name) if necessary.
- Click [OK].
- Then start a new check run.