Cause
Within a signal, there are connection definition points with different connection designations.
Solution
- Locate the connection definition point in the schematic using the Go to (graphic) function from the popup menu in the Message management dialog.
- Delete the connection designation, or change its name, so that all connection designations within the signal are identical.
- Refresh the connections and then start a new check run.
Tip:
Use the function of connection numbering in order to assign connection designations automatically.