This functionality is only available for certain module packages. Info / Copyright

P004019: No sensor at input

Cause

No sensor can be determined for the PLC Input during target tracking. The cause for this can be an incorrect type of signal at the PLC input and/or at the sensor. The target tracking definition might also be missing at a terminal or plug upstream of the sensor.

Solution

  1. First double-click the PLC input and select the Symbol / function data tab in the Properties <...> dialog.
  2. Click [Logic].
  3. Check the Type of signal property for the PLC input in the Connection point logic dialog. This property must match the function definition! If, for example, you entered a PLC connection point with the function definition "PLC connection point, DI" or "PLC connection point (fluid), DI", the type of signal field must be set as a "Digital input".
  4. Also check whether the type of signal property on the sensor is set to "sensor".
  5. If a terminal or a plug is located between the sensor and the PLC input, also check the setting in the field Target tracking (PLC) to for this object. A "2" must be entered for the function connection point 1 and a "1" for function connection point 2.
  6. Refresh the connections and then start a new check run.