Cause
You connected at least one of the two pin function connection points to more components than the specified number.
Solution
Possibility 1
- Double-click the pin in the schematic and select the Symbol / function data tab in the Properties <...> dialog.
- In the Function data (logic) group box click [Logic].
- In the Connection point logic dialog, check which values are set in the Number of targets row for both function connection points of the pin.
- Increase the defined value for one or both function connection points based on your requirements.
Possibility 2
- Double-click the pin in the schematic and select the Symbol / function data tab in the Properties <...> dialog.
- In the Function data (logic) group box click [Logic].
- In the Connection point logic dialog, check which values are set in the Number of targets row for both function connection points of the pin.
- Delete the excess components placed for each pin function connection point in the schematic.
Update the connections.
If required, start a new check run.