Causes
Within a configuration project a rack is not connected to the racks of the same workstation.
Or within a configuration project a rack is connected to the other racks of the same workstation with a different connection than a bus extension cable. This means that at least one of the bus ports connected to each other is not assigned to the bus system setting "Local-Bus: Extension". This setting is required when the racks are assigned to the same station.
Solution
Possibility 1
- Locate the PLC box of the rack '<x>' in the schematic using the Go to (graphic) functionality that is provided by the popup menu of the Message management dialog.
- Connect a bus port of this rack with a bus port of a different rack within the same workstation, so as to form autoconnecting lines.
- Call up the property dialog of the first bus port.
- Bring the Bus data tab to the front.
- Select the "Local-Bus: Extension" entry from the Bus system drop-down list.
- Click [OK].
- Repeat the settings described under Point 3 to Point 6 for the second bus port.
- Update the connections.
- If required, start a new check run.
Possibility 2
- Locate the PLC box of the rack '<x>' in the schematic using the Go to (graphic) functionality that is provided by the popup menu of the Message management dialog.
- Call up the properties dialog of the bus port that is connected to the bus port of another rack within the same workstation.
- Bring the Bus data tab to the front.
- Select the "Local-Bus: Extension" entry from the Bus system drop-down list.
- Click [OK].
- Locate the bus port connected to the first bus port in the schematic by selecting the function Go to 2nd coordinate from the popup menu of the message management.
- Repeat the settings described under Point 2 to Point 5 for the second bus port as well.
- Update the connections.
- If required, start a new check run.
Possibility 3
- Open the property dialog of the PLC box for one of the two racks.
- Bring the PLC structure data tab to the front.
- Change the workstation name.
- Click [OK].
- Update the connections.
- If required, start a new check run.