Cause
You specified in the Cable Properties dialog that only one PE / PEN conductor is permitted in the cable. The cable actually has several PE / PEN conductors, however.
Solution
Possibility 1
Change the potential type at the connection points of the functions that lead to PE or PEN conductors appearing multiple times in the cable.
- Call up the respective property dialog of the functions that are the source and / or target of the cable.
- For each function bring the Symbol / function data tab to the front, and click the [Logic] button.
- In the Connection point logic dialog at the function connection points check the value in the Potential type field.
- Then select a different potential type, for example "Undefined", at the function connection points with the value "PE" or "PEN" assigned several times.
- Confirm your entries.
Possibility 2
You allow multiple PE or PEN conductors in the cable.
- Double-click the cable definition line in the schematic.
- Activate the Allow multiple PE conductors check box in the property dialog of the cable.
Update the connections.
If required, start a new check run.