...Bundle / Network ID = '<x>', Bus master / bus coupler = '<y>', To bus master / bus coupler ID = '<z>', Bus system = '<u>', Position / Bus ID = '<v>', Data transfer rate = '<w>', Subslot = '<r>', DNS/PROFINET device name = '<s>'
Cause
Several causes are possible:
- PLC boxes with communication units are still contained in your project.
- Or you have imported an old project with PLC boxes that contain communication units.
- Or you have imported old macros that contain PLC boxes with communication units.
Solution
You may handle the data as you wish:
- Create, for example, a new bus port or use an existing bus port and there enter the data found that are displayed in the placeholders of the message.
- Subsequently remove the existing communication units at the PLC boxes by means of the following commands: File > Extras > Command group Organize > Project > Command group Optimize > Compress project.
- Import the PLC data again.
Note:
Using a new check run (any desired scheme) this module-specific message can be deleted from the message management dialog.