Cause
A PLC connection point with incomplete UDT data was determined within a CPU. In this concrete case a value is entered at the PLC connection point in the Symbolic address: UDT (name) property. However, the value of the data type is missing for the Symbolic address: UDT (Data type) property.
Solution
- Locate the PLC connection point in the schematic using the Go to (graphic) functionality that is provided by the popup menu of the Message management dialog.
- Open the property dialog of the PLC connection point.
- In the property table enter the data type in the field Symbolic address: UDT (data type). This value must be the same at all PLC connection points within the CPU where the property Symbolic address: UDT (name) has an identical value.
- Click [OK].
- If required, start a new check run.