P001026: Unconnected distributed terminals with same designation

Cause

The schematic contains distributed terminals that are not connected with each other although they have the same designation. The Connect associated distributed terminals automatically project-specific setting may not be activated.

Solution

  1. Select the commands File > Settings and in the tree view of the dialog Settings track the device in the Projects > "Project name" > Devices folder structure.
  2. Click on the setting area Terminals (distributed terminals), and activate the Connect associated distributed terminals automatically check box.
  3. Click [OK] in the dialog.
  4. Update the connections.
  5. If required, start a new check run.