Cause
The address areas of two subdevices of a PLC card are defined in such a way that their address areas overlap.
Solution
- Locate the PLC box of the PLC card in the schematic via the popup menu of the Message management dialog.
- Call up the property dialog of the PLC box and bring the first tab to the front.
- In the properties table modify the values in the fields PLC subdevice x: Start address (...) and PLC subdevice x: Data length (...) in such a way that an overlap of the address areas is impossible.
- Confirm your entries.
- If required, start a new check run.