Cause
The power dissipation layout in the air-conditioning field <x> of an enclosure (enclosure interior) is uneven due to the location of the part placements. The power dissipation center lies either in the top half or the bottom half <y> of the air-conditioning field.
Solution
- Locate the corresponding enclosure in the layout space using the Go to (graphic) functionality from the popup menu in the Message management dialog.
- Move the part displacements in the enclosure so that the power dissipation is as even as possible in the complete air-conditioning field.
- If required, start a new check run.