You have opened a project. You have opened a navigator that displays device data. Select a device tag. Select the New functions popup menu item.
In this dialog you generate multiple functions in the respective navigator for a new or existing DT according to a particular numbering pattern. This functionality is only available for particular functions (terminals, pins, coil and relay contacts, device, and PLC connections and busbars). Functions without connection points (for example PLC connection points with the function definition "PLC connection point, internal, general") cannot be generated with this functionality. Depending on the selected function definition, the numbering pattern defines either terminal, contact, or connection point designations.
Overview of the main dialog elements:
The full DT to which the function will be assigned is displayed in this field. The DT of the device you selected in the navigator is displayed. You can change the DT or enter a new DT.
Enter the numbering pattern in this field. For terminals, plugs, and coil contacts, the numbering pattern determines the terminal, plug, and coil contact designations. For other functions, the numbering pattern defines the connection point designations.
You have selected a terminal with two connection points as the function definition.
Numbering pattern |
Result |
---|---|
|
10 terminals with terminal designations |
You have selected a power switch with two connection points as the function definition.
Numbering pattern |
Result |
---|---|
|
3 power NO contacts with connection point designations |
You have selected a terminal with two connection points as the function definition. The numbering begins with the start value 1a, the numbering sequence is 1a,1b the numbering range is from 2a to 8b, and the last numbering value is 8b.
Numbering pattern |
Result |
---|---|
|
16 terminals with terminal designations |
This field contains the function definition used for the new functions. The [...] button opens the Function definitions dialog where you can select a different function definition.
The value in this field defines how many connection points every new function possesses. The number of connection points depends on the selected function definition.
The value in this field defines how many new functions are generated. The number of new functions depends on the numbering pattern and the number of connection points defined in the function definition.
If this check box is activated, multi-level terminals are formed from the generated terminals.
The value in this field defines how many levels each generated multi-level terminal has.
If the check box is selected, the terminals are numbered by level. If the check box is deselected, the terminals are numbered by terminal.
You have selected a terminal with two connection points as the function definition. You have carried out the following entries in the further fields:
Numbering pattern:
Multi-level terminal: Check box activated
Number of levels:
16 terminals are generated from which eight multi-level terminals with two levels each are formed. The following terminal designations are generated depending on the Number by levels check box.
Number by levels |
Result: Terminal designation [Level] |
---|---|
Yes, the check box is selected |
Level 2: Level 1: |
No, the check box is deselected |
Level 2: Level 1: |
See also
Automatically Generating Functions Using a Numbering Pattern