Cause
No address was specified at a PLC connection point that is an input or output.
Note:
Other PLC connection points, for example connection points for the card power supply are not checked.
Solution
- In the Properties <...> dialog of the PLC connection point, enter the address in the field by the same name.
- If required, start a new check run.