Cause
In the parts database to be checked a part was found at which a function template is defined with the "Network / bus cable connection point" function definition. No value is stored for the Plug designation property at this function template.
Solution
- In the message management dialog mark the line with the message and select the Properties popup menu item.
The Parts management dialog is opened, the respective part is already marked in it. - Bring the Function templates tab with the Device selection (function templates) table to the foreground.
- Enter a value in the Plug designation field for the bus port at the function template.
- Close the parts management, save the modified data, and carry out a parts synchronization.
- If required, start a new check run.