Cause
During the calculation of the fill capacity for wire ducts EPLAN determined that there is a missing diameter entry for a used individual connection or a used cable.
The diameter is invalid if there is either no diameter entry at all or if the value for the diameter is outside an area between 0 and 500 mm.
Solution
- Enter a valid diameter for the individual connection or cable.
- Then start a new check run and update the fill capacity again (menu items Project data > Connections > Update fill capacity).
Note:
Using a new check run (any desired scheme) this module-specific message can be deleted from the message management dialog.