In building automation in accordance with the standards VDI 3814 and DIN EN ISO 16484-3 it is usual to output the information required for the planning and implementation of building automation systems and instrumentation and control systems in function lists. Special basic projects, forms as well as properties for pre-planning are available in EPLAN to support these function lists.
Function lists
The form for the function lists is divided into sections and columns. The properties displayed in the form are sorted by sections. In EPLAN the properties specified by the standard are mapped in part by fixed defined EPLAN properties and in part by user-defined properties. Section 1 contains fixed defined EPLAN properties for the display of PLC inputs and outputs. Sections 2 to 8 contain user-defined properties. These properties are already predefined in the basic project for building automation and are available for immediate use when you use this template.
The EPLAN properties listed below are used in Section 1 of the form for function lists. These properties are determined from the entries in the PLC tab (in the properties dialog of planning objects). The combination of the entries in the columns Direction, Data type and Counter specify which type of PLC input or output this is.
Section |
Column |
Input / output functions |
EPLAN property |
---|---|---|---|
1 |
1 |
Binary output: switching / actuating |
Total number of digital PLC outputs (ID 44029) |
1 |
2 |
Analog output: actuating |
Total number of analog PLC outputs (ID 44031) |
1 |
3 |
Binary input: signaling |
Total number of digital PLC inputs (ID 44028) |
1 |
4 |
Binary input: counting |
Total number of PLC counter inputs (ID 44059) |
1 |
5 |
Analog input: measuring |
Total number of analog PLC inputs (ID 44030) |
In order to output function lists for building automation in accordance with the standard VDI 3814, use the report type "Pre-planning: Planning object overview" and assign the form F40_VDI3814.f40 or F40_VDI3814_A.f40 to it.
Function lists in BACnet-compliant representation
The function lists for the building automation can also be output in BACnet-compliant representation in accordance with the standards VDI 3814 and EN ISO 16484-5. In this form of representation the PCT loop functions not only describe the measuring and user functions but also the software functions of PCT loops.
For a BACnet-compliant representation a PCT loop function must be created for each software function (each PLC input and output) in the pre-planning navigator and the PCT loop functions must be located below the PCT loops. By default these PCT loop functions have a row in the PLC tab. The assignment of a PLC address is not necessarily required in this case.
For the output of function lists in BACnet-compliant representation some forms are now also have available in the master data (for example F40_VDI3814_1.f40, F40_VDI3814_1_en_US.f40. etc.).
Graphical display of automation schemes
You can draw a schematic overview (automation scheme) of the planned part area in the EPLAN project on a page of the type "P&I diagram". In this overview the amount of used or required inputs / outputs per planning object can be displayed. To do so use a property arrangement at the functions placed in the automation scheme in which the properties for the total number of the PLC inputs and outputs (for example Total number of digital PLC outputs (ID 44029)) are selected for display. This information is usually displayed path-wise below the drawing. In the property arrangement for properties that output the total number of the PLC inputs and outputs, activate the display property Zero as blank if zero values are not to be shown anymore in the listing of the overall numbers.
To implement such a path-wise display you have to change the display settings and select an automatic Y coordinate. To do so activate the display property Y-coordinate automatic (path) in the property arrangement. The value of the Y coordinate (in relation to the point of origin of the page) is determined in the Property arrangement: Y coordinate automatic (path) (ID 12062) property. This property is available for plot frames and pages.
A line-by-line display (for example for projects to the NFPA standard) is also possible. To do so activate the display property X coordinate automatic (path) in the property arrangement. The value of the X coordinate (in relation to the point of origin of the page) is determined in the Property arrangement: X coordinate automatic (path) (ID 12063) property. This property is available for plot frames and pages.